Energy-saving glycol chiller/low temperature chiller/low temperature glycol chiller

Product DescriptionScrew Type Water Cooled ChillerCooling 130-420kWApplication areasIndustry process, precision,traditional manufacturing, food processing, government project, pharmacetical.Characteristics29 sizes available ranging from 130 kW to 2500 kW cooling capacity. Acting as multi-function unit such as cooling, heati

Featured Products

Product Description


Screw Type Water Cooled Chiller
Cooling 130-420kW


Application areas

Industry process, precision,traditional manufacturing, food processing, government project, pharmacetical.

Characteristics

29 sizes available ranging from 130 kW to 2500 kW cooling capacity.

 Acting as multi-function unit such as cooling, heating, sanitary hot water separately or simultaneously.

Wide application as hotel, apartment, villa, factory, shopping center, office building, school, etc.

Semi- hermetic screw compressor for the whole range. Each compressor is equipped with a crankcase heater and a built-in electronic

protection with temperature sensor located directly in the motor winding and on the discharge line.

The refrigerant circuit is complete with sight glass, filter drier, high and low pressure gauges, solenoid valve, electronic expansion valve, high and low pressure switch.

Shell and tube dry expansion type condenser, factory insulated with flexible close cell material.
  
Shell and tube evaporator, higher efficiency less water consumption, easy maintenance and cleaning, factory insulated with flexible close cell material.

The electric panel consists of compressor breaker, compressor contactor, phase sequence relay, control circuit breaker, microprocessor control with function display.

LCD display, touch screen control panel as standard.

Automatic operation dramatically reducing maintenance cost thanks to reliable microprocessor system.

An infinitely variable capacity control system that is capable of exactly matching the demand requirement of the system is to be supplied. This system is to provide precise and stable control of supply water temperature over the complete range of operating conditions.

Optional
Desuperheater as optional.
Electronic controller with BMS system.

Technical Data
Screw Type Water Cooled Chiller



* Performance values refer to the following conditions:
Condenser water inlet/outlet temperature: 30ºC/35ºC, evaporator water inlet/outlet temperature: 12ºC/7ºC.
    
** Noise level measured in free field condition at distance of 1 meter.

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours
.75pt;text-align:center;"> Runnig weight(kg)1370145019602180
Air Cooled Chiller Unit (Heat recovery-low temp.type/-15ºC)
Model   ESGA30SXTY33SXTY38SXTY40SXTY
30SXVTY33SXVTY38SXVTY40SXVTY
 RefrigerantR22R404AR22R404AR22R404AR22R404A
Rated cooling capacity×1000 kcal/h89.6 88.5 98.4 99.2 116.2 114.4 122.9 121.0 
kW104.2 102.9 114.4 115.4 135.2 133.0 142.9 140.7 
USRT29.6 29.3 32.5 32.8 38.4 37.8 40.6 40.0 
Comp.input PowerX QTY(KW)58.4×171.9×163.6×180.8×171.6×192.4×175.3×197.4×1
 Power supply3φ-380V-50Hz
Protection devicePhase Peversion Protection,Phase Lack Protection,Overload Current Protection,Discharge Air Temperature Protection
Number of refrigeration circuits1111
Capacity control0,50,75,100
Refrigerant Charge(kg)48566875
Air Coled Heat ExchangerRipple Aluminum Fins Around Copper Pipe

Water Cooled Heat Exchanger
Dia.Of Pipe(inch)3″3″3″3″
Water Side Max Pressure (Mpa)1
Chilled Liquid Folw (m3/h)17.9 17.7 19.7 19.8 23.2 22.9 24.6 24.2 
Water Pressure drop(Kpa)61 61 64 64 66 66 66 66 
Axial FanAir Flow×1000  m3/h56.856.880.480.480.480.485.280.4
PowerX QTY(KW)1.2×41.2×42.0×42.0×42.0×42.0×41.2×62.0×4
 Running noise dB(A)72727272
 Total Weight(kg)2610270027802860
Runnig weight(kg)2830292030203250
Heat Recovery Parameters
 Refrigerant Charge(kg)51 59 71 78 
Heaet Reciaimed Volume×1000 kcal/h26.9 26.6 29.5 29.8 34.9 34.3 36.9 36.3 
kW31 31 34 35 41 40 43 42 
USRT8.9 8.8 9.8 9.8 11.5 11.3 12.2 12.0 
Heat RecovererDia.Of Pipe(inch)2″2″2″2″
Water Side Max Pressure (Mpa)1
Reclaimed Water Flow(m3/h)5.4 5.3 5.9 6.0 7.0 6.9 7.4 7.3 
Water Pressure drop(Kpa)26 26 26 26 26 26 26 26 
 Total Weight(kg)2730 2820 2900 2980 
 Runnig weight(kg)2950 3040 3140 3370 



Air Cooled Chiller Unit (Heat recovery-low temp.type/-15ºC)
Model   ESGA45SXTY50SXTY55SXTY60SXTY
45SXVTY50SXVTY55SXVTY60SXVTY
 RefrigerantR22R404AR22R404AR22R404AR22R404A
Rated cooling capacity×1000 kcal/h134.4 132.4 145.4 145.8 160.0 157.4 190.5 187.1 
kW156.3 154.0 169.0 169.6 186.1 183.1 221.6 217.6 
USRT44 44 48 48 53 52 63 62 
Comp.input PowerX QTY(KW)82.9×1106.9×190.4×1116.9×2100.6×1127.3×1116.8×1150.7×1
 Power supply3φ-380V-50Hz
Protection devicePhase Peversion Protection,Phase Lack Protection,Overload Current Protection,Discharge Air Temperature Protection
Number of refrigeration circuits1111
Capacity control0,50,75,100
Refrigerant Charge(kg)80 86 95 105 
Air Coled Heat ExchangerRipple Aluminum Fins Around Copper Pipe

Water Cooled Heat Exchanger
Dia.Of Pipe(inch)4″4″4″4″
Water Side Max Pressure (Mpa)1
Chilled Liquid Folw (m3/h)26.9 26.5 29.1 29.2 32.0 31.5 38.1 37.4 
Water Pressure drop(Kpa)42 42 54 54 44 44 52 52 
Axial FanAir Flow×1000  m3/h85.285.2120.6120.6120.6120.6160.8160.8
PowerX QTY(KW)1.2×61.2×62.0×62.0×62.0×62.0×62.0×82.0×8
 Running noise dB(A)72727272
 Total Weight(kg)3220324035003620
Runnig weight(kg)3380362038804010
Heat Recovery Parameters
 Refrigerant Charge(kg)85 91 100 110 
Heaet Reciaimed Volume×1000 kcal/h40.3 39.7 43.6 43.7 48.0 47.2 57.2 56.1 
kW47 46 51 51 56 55 66 65 
USRT13.3 13.1 14.4 14.5 15.9 15.6 18.9 18.6 
Heat RecovererDia.Of Pipe(inch)2-1/2″2-1/2″2-1/2″2-1/2″
Water Side Max Pressure (Mpa)1
Reclaimed Water Flow(m3/h)8.1 7.9 8.7 8.7 9.6 9.4 11.4 11.2 
Water Pressure drop(Kpa)26 26 26 26 27 27 27 27 
 Total Weight(kg)3360 3390 3650 3770 
 Runnig weight(kg)3520 3770 4030 4160 


Air Cooled Chiller Unit (Heat recovery-low temp.type/-15ºC)
Model   ESGA50DXTY60DXTY65DXTY
50DXVTY60DXVTY65DXVTY
 RefrigerantR22R404AR22R404AR22R404A
Rated cooling capacity×1000 kcal/h147.0 147.0 179.1 177.0 196.8 198.4 
kW171.0 171.0 208.3 205.9 228.9 230.7 
USRT49 49 59 59 65.1 65.6 
Comp.input PowerX QTY(KW)47.9×260.8×258.4×271.9×263.6×280.8×2
 Power supply3φ-380V-50Hz
Protection devicePhase Peversion Protection,Phase Lack Protection,Overload Current Protection,Discharge Air Temperature Protection
Number of refrigeration circuits222
Capacity control0,25,37.5,50,62.5,75,87.5,100
Refrigerant Charge(kg)110115124
Air Coled Heat ExchangerRipple Aluminum Fins Around Copper Pipe

Water Cooled Heat Exchanger
Dia.Of Pipe(inch)4″4″4″
Water Side Max Pressure (Mpa)1
Chilled Liquid Folw (m3/h)29.4 29.4 35.8 35.4 39.4 39.7 
Water Pressure drop(Kpa)54 54 55 55 65.0 65.0 
Axial FanAir Flow×1000  m3/h113.6113.6113.6113.6160.8 160.8 
PowerX QTY(KW)1.2×81.2×81.2×81.2×82.0×82.0×8
 Running noise dB(A)757575
 Total Weight(kg)459047804850
Runnig weight(kg)476049505130
Heat Recovery Parameters
 Refrigerant Charge(kg)115120129
Heaet Reciaimed Volume×1000 kcal/h44.1 44.1 53.7 53.1 59.0 59.5 
kW51 51 63 62 68.7 69.2 
USRT14.6 14.6 17.8 17.6 19.5 19.7 
Heat RecovererDia.Of Pipe(inch)2-1/2″2-1/2″2-1/2″
Water Side Max Pressure (Mpa)1
Reclaimed Water Flow(m3/h)8.8 8.8 10.7 10.6 11.8 11.9 
Water Pressure drop(Kpa)30 30 30 30 34.0 34.0 
 Total Weight(kg)475049405010
 Runnig weight(kg)492051105290


Air Cooled Chiller Unit (Heat recovery-low temp.type/-15ºC)
Model   ESGA75DXTY80DXTY90DXTY
75DXVTY80DXVTY90DXVTY
 RefrigerantR22R404AR22R404AR22R404A
Rated cooling capacity×1000 kcal/h232.5 228.8 245.6 241.9 268.8 264.7 
kW270.5 266.1 285.7 281.3 312.6 307.8 
USRT77 76 81 80 88.9 87.5 
Comp.input PowerX QTY(KW)71.6×292.4×275.3×297.4×282.9×2106.9×2
 Power supply3φ-380V-50Hz
Protection devicePhase Peversion Protection,Phase Lack Protection,Overload Current Protection,Discharge Air Temperature Protection
Number of refrigeration circuits222
Capacity control0,25,37.5,50,62.5,75,87.5,100
Refrigerant Charge(kg)135147161
Air Coled Heat ExchangerRipple Aluminum Fins Around Copper Pipe

Water Cooled Heat Exchanger
Dia.Of Pipe(inch)4″4″4″
Water Side Max Pressure (Mpa)1
Chilled Liquid Folw (m3/h)46.5 45.8 49.1 48.4 53.8 52.9 
Water Pressure drop(Kpa)54 54 55 55 65.0 65.0 
Axial FanAir Flow×1000  m3/h160.8160.8170.4170.4170.4 170.4 
PowerX QTY(KW)2.0×82.0×81.2×121.2×121.2×121.2×12
 Running noise dB(A)757575
 Total Weight(kg)536055105660
Runnig weight(kg)558058306100
Heat Recovery Parameters
 Refrigerant Charge(kg)140152166
Heaet Reciaimed Volume×1000 kcal/h69.8 68.6 73.7 72.6 80.6 79.4 
kW81 80 86 84 93.8 92.3 
USRT23.1 22.7 24.4 24.0 26.7 26.3 
Heat RecovererDia.Of Pipe(inch)2-1/2″2-1/2″2-1/2″
Water Side Max Pressure (Mpa)1
Reclaimed Water Flow(m3/h)14.0 13.7 14.7 14.5 16.1 15.9 
Water Pressure drop(Kpa)30 30 30 30 34.0 34.0 
 Total Weight(kg)552056705820
 Runnig weight(kg)574059906260

Air Cooled Chiller Unit (Heat recovery-low temp.type/-15ºC)
Model   ESGA95DXTY105DXTY125DXTY
95DXVTY105DXVTY125DXVTY
 RefrigerantR22R404AR22R404AR22R404A
Rated cooling capacity×1000 kcal/h290.7 291.7 319.9 314.9 381.1 374.3 
kW338.1 339.3 372.1 366.2 443.2 435.3 
USRT96 96 106 104 126.0 123.8 
Comp.input PowerX QTY(KW)90.4×2116.9×2100.6×2127.3×2116.8×2150.7×2
 Power supply3φ-380V-50Hz
Protection devicePhase Peversion Protection,Phase Lack Protection,Overload Current Protection,Discharge Air Temperature Protection
Number of refrigeration circuits222
Capacity control0,25,37.5,50,62.5,75,87.5,100
Refrigerant Charge(kg)175186195
Air Coled Heat ExchangerRipple Aluminum Fins Around Copper Pipe

Water Cooled Heat Exchanger
Dia.Of Pipe(inch)4"4"4″×2
Water Side Max Pressure (Mpa)1
Chilled Liquid Folw (m3/h)58.1 58.3 64.0 63.0 76.2 74.9 
Water Pressure drop(Kpa)54 54 55 55 65.0 65.0 
Axial FanAir Flow×1000  m3/h241.2241.2241.2241.2321.6 321.6 
PowerX QTY(KW)2.0×122.0×122.0×122.0×122.0×162.0×16
 Running noise dB(A)757575
 Total Weight(kg)572058606320
Runnig weight(kg)604064806900
Heat Recovery Parameters
 Refrigerant Charge(kg)180191200
Heaet Reciaimed Volume×1000 kcal/h87.2 87.5 96.0 94.5 114.3 112.3 
kW101 102 112 110 133.0 130.6 
USRT28.8 28.9 31.7 31.2 37.8 37.1 
Heat RecovererDia.Of Pipe(inch)2-1/2″2-1/2″2-1/2″×2
Water Side Max Pressure (Mpa)1
Reclaimed Water Flow(m3/h)17.4 17.5 19.2 18.9 22.9 22.5 
Water Pressure drop(Kpa)30 30 30 30 34.0 34.0 
 Total Weight(kg)588060206480
 Runnig weight(kg)620066407060

NOTE:
1. Rated Cooling Capacity Based on: DB Temperature 35ºC/WB Temperature 24ºC
Chilled water in/outlet temp. -10ºC/-15ºC, Fouling factor: 0.088.°C/KW.
2. Chilled Water Range: -15~-5ºC; Ambient Temperature: 5ºC~43ºC;
3. Heat recovery unit water in/out temperature: 50ºC/55ºC;
4. Specifications are subject to change without notice for further improvement.


4.Eurostars water chiller protection devices
1)Phase reversion protection, 
2)Phase lack protection, 
3)Overload current protection,
4)Discharge air temp. protection, 
5)Low & High pressure protection, 
6)Low temp. protection,
Low Temperature Glaze Powder Melamine Formaldehyde Resin Melamine Powder 99.9% Urea Moulding Compound Melamine Resin Molding Compound A5 Melamine Moulding Compound Urea Melamine Molding Compounds Melamine Glazing Powder 99.8% Melamine White Powder Melamine Compound Urea Moulding Powder

Previous:Ultra-low temperature freezer, ultra-low temperature freezer (RAY-27500)

Next:Multifunctional low temperature tester-low temperature test

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours